User manual
We do more with electricity.
Micrologic A Schneider Electric
1
Discovering your control unit 2
Identifying your control unit 2
Overview of functions 4
Setting your control unit 10
Selecting the type of neutral protection 10
Setting procedure 11
Setting the Micrologic 2.0 A control unit 12
Setting the Micrologic 5.0 A control unit 13
Setting the Micrologic 6.0 A control unit 14
Setting the Micrologic 7.0 A control unit 15
Fault and status indications 16
Resetting the fault indications
and checking battery status 16
Testing the earth-fault
and earth-leakage functions 17
Menus 18
Accessing the menus 18
Measuring phase currents 19
Displaying the maximum current values 20
Resetting the maximum current values 21
Viewing the settings 22
Technical appendix 24
Tripping curves 24
Changing the long-time rating plug 26

c P for "power meter"
c H for "harmonic meter"
c no indication: no measurements
Micrologic 2.0 A: basic protection and ammeter
Long time + Instantaneous
Micrologic 5.0 A: selective protection and ammeter
Long time + Short time + Instantaneous
E51385A
E51354A
0 Ir Isd I
t
0 Ir I
t
IiIsd
Micrologic 6.0 A: selective + earth-fault protection and
ammeter
E51387A
E51354A
E51395A
0 Ir I
t
IiIsd
Long time + Short time
+ Instantaneous
Earth-fault protection
Micrologic 7.0 A: selective + earth-leakage protection and
ammeter
E51388A
E51354A
E51452A

.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
x Ir
2
2.5
3
4
5
6
1.5
setting
Isd
8
10
Micrologic 5.0 A
40
100
%
%
menu

x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
on

I
2
t
.
2
.
4
.
4
.
1
.
3
.
1
0
I i

.
3
.
4
.
4
.
1
.
2
.
1
0
long time
alarm
ground fault
setting
4
test
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In

12
15
off
2
B
C
D
E
F
G
H
I
Ig
A
on

I
2
t
.
2
.
3
.
4
.
4
.
1
.

.98
delay
short time
off
long time
alarm
setting
earth leakage
test
.4
.5
.6
.7
.8
.9
.95
1
Ir
x In
tr
(s)
.5
1
2
4
8
12
16
20
at 6 Ir

2
.
3
.
1
0
x In
3
4
6
8
10
12
15
off
2
1
2
3
5
7
10
20
30
.5
I∆n
800
∆I
60
140

21 earth-fault tripping delay tg
22 earth-leakage pick-up I∆n
23 earth-leakage tripping delay ∆t
Indications
24 LED indicating long-time tripping
25 LED indicating short-time tripping
26 LED indicating earth-fault
or earth-leakage tripping
27 LED indicating auto-protection tripping
28 LED indicating an overload
Navigation
29 navigation button to change menus
30 navigation button to view menu contents
31 button for fault-trip reset and battery test
Test
32 test button for earth-fault and earth-leakage
protection
33 test connector
Presentation
E51389A
E51390A
E51391A
Micrologic 7.0 A Micrologic 2.0 A
Micrologic 5.0 A
E51394A
E51393A
Micrologic 6.0 A
E51392A
3
2

)
x In
at

6
Ir
7
11
12
M
ic
r
o
l
o
g
ic
7
.0
A
4
0
1
0
0
%
%
m
e
n

20
tr
(s)
at 6 Ir
24
x Ir
2
2.5
3
4
5
6
8
10
1.5
setting
Isd
14
15
18
33
28
7
Micrologic 7.0 A
40
100
%
%
menu
delay

4
5
6
8
10
1.5
x
In
3
4
6
8
10
12
15
off
2
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
.4

t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
Isd
32
.95
.98
setting delay
short time
I i
tsd
(s)
long time
alarm
.4
.5
.6
.7
.8
.9
1

.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
x In
3
4
6
8
10
12
15
off
2
14
15
16

0
off
long time
alarm
Ir
x In
ground fault
B
C
D
E
F
G
H
I
Ig
tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0

8
10
12
15
off
test
instantaneous
15
14
17
16
21
20
28
7
19
32
33
2
Micrologic A Schneider Electric
4
Discovering your
control unit
Protection settings
Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.
Long-time protection
The long-time protection function protects cables (phases and neutral)
against overloads. This function is based on true rms measurements.
Thermal memory

E51359A
Micrologic 5.0 A, 6.0 A,
7.0 A
1
2
3
4
5
0
Ir Isd I
t
Ii
I
2
t off
I
2
t on
E51386A
E51396A
Micrologic 6.0 A Micrologic 7.0 A
1. current setting Ir
(long time)
2. tripping delay tr
(long time) for 6 x Ir
3. pick-up Isd (short time)
4. tripping delay tsd
(short time)
5. pick-up Ii
(instantaneous)

c this function carries out true rms measurements.
c the I
2
t ON and I
2
t OFF options enhance discrimination with downstream
protection devices
c use of I
2
t curves with short-time protection:
v I
2
t OFF selected: the protection function implements a constant time curve;
v I
2
t ON selected: the protection function implements an I
2
t inverse-time
curve up to 10 Ir. Above 10 Ir, the time curve is constant.
c zone selective interlocking (ZSI)
The short-time and earth-fault protection functions enable time discrimination
by delaying the upstream devices to provide the downstream devices the time
required to clear the fault. Zone selective interlocking can be used to obtain total
discrimination between circuit breakers using external wiring.
Short-time pick-up Isd and tripping delay tsd
Micrologic control unit 2.0 A, 5.0 A, 6.0 A and 7.0 A
pick-up Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
accuracy ± 10 %
time delay settings I
2

The portable test kit can be used to test
the wiring between circuit breakers
for the zone selective interlocking function.
Micrologic A Schneider Electric
6
Discovering your
control unit
Protection of the fourth pole on four-pole circuit breakers
Protection of the neutral conductor depends on the distribution system.
There are three possibilities.
Type of neutral Description.
Neutral unprotected The distribution system does not require protection
of the neutral conductor.
Neutral protection The cross-sectional area of the neutral conductor
at 0.5 In is half that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to half the setting value
c the short-time pick-up Isd for the neutral is equal
to half the setting value
c the instantaneous pick-up Isd (Micrologic 2.0 A)
for the neutral is equal to half the setting value
c the instantaneous pick-up Ii (Micrologic 5.0 A / 6.0 A /
7.0 A) for the neutral is equal to the setting value.
Neutral protection The cross-sectional area of the neutral conductor is equal
at In to that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to the setting value
c the short-time pick-up Isd for the neutral is equal to
the setting value
c the instantaneous pick-ups Isd and Ii for the neutral

time delay settings I
2
t OFF 0 0.1 0.2 0.3 0.4
(ms) at 10 In (*) I
2
t ON 0.1 0.2 0.3 0.4
I
2
t ON or tg (max resettable time) 20 80 140 230 350
I
2
t OFF tg (max break time) 80 140 200 320 500
* In: circuit-breaker rating
Micrologic A Schneider Electric
7
Current protection and alarms
Earth-leakage protection on Micrologic 7.0 A
c the earth-leakage protection function primarily protects people against indirect
contact because an earth-leakage current can provoke an increase in the potential
of the exposed conductive parts. The earth-leakage pick-up value I∆n is displayed
directly in amperes and the tripping delay follows a constant-time curve
c an external rectangular sensor is required for this function
c this function is inoperative if the long-time rating plug is not installed
c d protected against nuisance tripping.
c k DC-component withstand class A up to 10 A.
Pick-up value I∆n and tripping delay ∆t
Micrologic control unit 7.0 A
pick-up I∆n 0.51235710 20 30
accuracy
0 to - 20 %

tsd
(s)
long time
alarm
test
800
earth leakage
1
2
3
5
7
10
20
30
∆t
(ms)
60
.5
140
230
350
I∆n
(A)
setting
x
Ir
2
2.5
3

15
off
2
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
instantaneous
40
%
%

%
%
100
1.125 x Ir
1 x Ir
0.8 x Ir
0.6 x Ir
0.4 x Ir
If no information is displayed on the screen,
see the technical appendix "Digital display".
Micrologic A Schneider Electric
9
Micrologic A Schneider Electric
10
Setting your control unit
Selecting the type
of neutral protection
On four-pole circuit breakers, it is possible to select the type of neutral protection
for the fourth pole:
c neutral unprotected (4P 3D);
c neutral protection at 0.5 In (3D + N/2);
c neutral protection at In (4P 4D).
E51383A
4P 3D
3D+N/2
4P 4D
Micrologic A Schneider Electric
11
Setting procedure
Setting procedure

%
%
m
e
n
u
Micrologic 7.0 A
4
0
1
0
0
%
%
m
e
n
u
2
A
Ir=
3
Micrologic 7.0 A
4
0
1
0
0
%
%

See the user manual for the portable
test kit
Micrologic A Schneider Electric
12
Setting your control unit
Setting the Micrologic 2.0 A
control unit
Set the threshold values
E51366A
E60365A
Set the tripping delay
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 and 5 for information
on the available settings
E51368A
E60366A
E51370A
1
In = 2000 A
In = 2000 A
In = 2000 A
Ir = 0.7 x In = 1400 A
Isd = 3 x Ir = 4200 A
alarm
x Ir
2
2.5
3
4

8
12
16
20
tr
(s)
at 6 Ir
24
tr = 1 second
0 I
t
tr
Micrologic A Schneider Electric
13
Setting the Micrologic 5.0 A
control unit
Set the threshold values
E51366A
E60367A
Set the tripping delay
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 and 5 for information
on the available settings
E60368A
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
Isd = 2 x Ir = 2800 A
.4

8
10
12
15
off
2
instantaneous
tr = 1 second
tsd = 0.2 seconds
short time
long time
alarm
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
delay
tsd
(s)
on

I

I
t
Ir
Isd
Ii
0
I
t
I
2
t

ON curve
I
2
t

OFF curve
1
In
=
2
0
0
0
A
In = 2000 A
Thresholds
E51375A
E51376A

in this example is 2000 A.
See pages 4 to 6 for information
on the available settings.
E51373A
E51372A
Ir
Isd
Ii
0
I
t
Ir
Isd
Ii
0
I
t
I
2
t

ON curve I
2
t

OFF curve
Set the tripping delay
E60372A
E51376A
E51375A

.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
B
C
D
E
F
G
H
I
Ig

1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
delay
tsd
(s)
on

I
2
t
.2
.3
.4
.4
.2
.3
.1
0
off
tg
(s)


ON curve I
2
t

OFF curve
Micrologic A Schneider Electric
15
Setting the Micrologic 7.0 A
control unit
Set the threshold values
E51366A
E51420A
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 to 7 for information
on the available settings.
Set the tripping delay
E60373A
1
In
=
2
0
0
0
A
In = 2000 A
.4
.5

8
10
12
15
off
2
instantaneous
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
Isd = 2 x Ir = 2800 A
I∆n = 1 A
1
2
3
5
7
10
20
30
.5
I∆n
(A)
test
short time
long time
alarm
ground fault
.5
1

140
230
350
tr = 1 second
tsd = 0.2 seconds
∆t = 140 milliseconds
I
2
t on I
2
t off
test
I
2
t

OFF curve
E51373A
E51372A
Ir
Isd
Ii
0
I
t
Ir
Isd
Ii
0
I

ON curve
0 I
t
I∆n
0 I
t
∆t
Micrologic A Schneider Electric
16
Fault and status
indications
The procedure for closing the circuit
breaker following a fault trip is presented
in the circuit-breaker user manual.
Resetting the fault indications
and checking battery status
If the battery needs to be changed, please
use the one with Schneider catalogue
number 33593 (characteristics given on the
battery compartment cover).
Resetting the fault indications
c determine why the circuit breaker tripped.
The fault indication is maintained until it is reset on the control unit.
v press the fault-trip reset button.
E51439A
v check the parameter settings of the control unit.
Checking the battery
E51441A
Press the battery-test button (same as the fault-trip reset button) to display
the battery status.

0
1
0
0
%
%
Micrologic A Schneider Electric
17
Testing the earth-fault and earth-
leakage functions
Charge and close the circuit breaker.
Using a screwdriver, press the test button for earth-fault and earth-leakage
protection. The circuit breaker should open.
E51410A
1
Micrologic 7.0 A
4
0
1
0
0
%
%
m
e
n
u
E51456A
Micrologic 7.0 A
4

Three menus may be accessed on Micrologic control units, providing the following
information:
c phase current measurements I1, I2, I3, neutral IN, earth-fault current Ig on the
Micrologic 6.0 A control unit and earth-leakage current I∆n on the Micrologic 7.0 A
control unit;
c maximeter current values for phases I1, I2, I3, neutral IN, the maximum earth-
fault current Ig on the Micrologic 6.0 A control unit and the maximum earth-leakage
current I∆n on the Micrologic 7.0 A control unit;
c protection settings and tripping delays.
Press the "menu" button
to access the maximum
current values measured
by the maximeter.
Press the "menu" button
to access the protection
settings and tripping
delays.
Press the "menu" button
to return to the current
measurements.
E51406A
E51407A
E51408A
4. The system returns
to the main
"Measurements" menu.
E51409A
40
100
%

displays the current value of the most
heavily loaded phase.
E51409A
Measuring phase currents
Display of current I1. Display of current I2.
E51425A
E51426A
Press the "arrow" button
to go on to current I2.
Press the "arrow" button
to go on to current I3.
Display of current I3.
Display of current Ig
(Micrologic 6.0 A) or
current I∆n
(Micrologic 7.0 A).
Press the "arrow" button
to go on to current IN if
the circuit breaker is
connected to the neutral.
E51427A
E51428A
Display of current IN.
The system returns to
the display of current I1.
E51429A
E51409A
40
100
%

%
A
Press the "arrow" button
to return to current I1.
"Measurements" menu
Phase 1 is the most heavily loaded.
Press the "arrow" button
to go on to the earth-fault
current Ig or the earth-
leakage current I∆n.
Micrologic A Schneider Electric
20
Menus
Maximum current values may be read in
the "Maximeter" menu.
If no particular action is taken, the system
returns to the main menu.
E51407A
Displaying the maximum
current values
Display of the
maximum I1 current.
Display of the
maximum I2 current.
E51430A
E51431A
Press the "arrow" button
to go on to the maximum
I2 current.
Press the "arrow" button

%
%
A
MAX
40
100
%
%
A
MAX
40
100
%
%
A
MAX
40
100
%
%
MAX
A
40
100
%
%
A
MAX
40
100

Press the "arrow" button
as many times as
required to select I2 max.
Press and hold the
"arrow" button down for
three to four seconds.
The current value flashes
during the reset, then
changes to the present
value (the new
maximum).
Select another value
to reset or return to
the main menu.
Press the "arrow" button
as many times as
required to select another
maximum value to reset
or return to the main
menu.
E51438A
40
100
%
%
A
Max
menu
40
100


n
Earth-fault tripping delay tg
Earth-leakage tripping delay

t
Micrologic control unit
Select the "Settings"
menu.
The Ir value is the first
displayed.
Press the "arrow" button
to go on to the tr value.
Press the "arrow" button
to go on to the
short-time Isd value.
Press the "arrow" button
to go on to the tsd
value.
Press the "arrow" button
to go on to the
instantaneous Isd
value.
Or
Press the "arrow" button
to go on to the Ig value.
Or
Press the "arrow" button
to go on to the tg value.
Or

5.0 A
6.0 A 7.0 A
2.0 A
Micrologic A Schneider Electric
23
Micrologic A Schneider Electric
24
Technical appendix
Tripping curves
Long-time and instantaneous protection (Micrologic 2.0 A)
E60369A
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05

2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
x In
tr = 0.5…24 s
Isd = 1.5…10 x Ir
Ir = 0.4…1 x In
Ii = 2…15 x In . OFF (1)
I
2
t OFF
x Ir
0.4
0.3
0.2
0. 1
I
2
t ON
0